8  Troubleshooting
8.1   Alarm
In the event of an error message try restarting the installation using the installation’s safety 
switch.
If restarting the heat pump does not help try rectifying the problem using the table below. 
Contact your installer (see ”References”) if you are unable to rectify the problem yourself. 
Message Meaning Cause Remedy
LOWPRESS 
ERROR
LOWPRESS ERROR - The com-
pressor stops and there is no 
hot water production.
Not enough fluid 
in the brine sys-
tem. Air in the 
brine system. 
Blocked filter in 
the brine system.
Contact your 
installer.
HIGHPRESS 
ERROR
HIGHPRESS ERROR - The com-
pressor stops and there is no 
hot water production.
Insufficiently 
opened radiator/
floor loop thermo-
stats.  
Air in the heating 
system. Blocked 
strainer in the 
heating system. 
Open radiator / 
floor loop thermo-
stats. Top up and 
bleed the heating 
system or contact 
your installer.
MOTOR P 
ERROR
Motor protection cut out. The 
compressor stops and there is 
no hot water production. 
Power failure 
caused by a 
blown fuse or the 
safety switch has 
deployed.
Check the fuses 
and reset the 
safety switch.
ALARM 
AUXILIARY 
HEATER
Overheating protection 
deployed.
Electrical fault. The 
safety switch has 
tripped. 
Contact your 
installer.
SENSOR 
OUTDOOR
Fault in outside sensor. To cal-
culate the supply temperature’s 
desired value, use 0°C instead.
Electrical fault. Contact your 
installer.
SENSOR 
FRONT
Incorrect supply sensor. 
Everything stops except the 
circulation pump for the heat-
ing system.
Electrical fault. Contact your 
installer.
SENSOR 
RETURN
Return sensor fault. Electrical fault. Contact your 
installer.