User manual ERC 113 refrigeration controller
Ser Service information settings
The parameters in the following section are READ ONLY and cannot be
changed by the user.
They provide information for technicians and OEM users.
NOTE: the only parameters that can be configured are: "oEL", "oEn", " oEH".
These parameters allow OEMs to enter their own product code.
"ACt" Accumulated Comp. run time
"AFt" Accumulated Fan run time
"ALt" Accumulated Light run time
"AEt" Accumulated ERC up time
"Sdi" DI
physcial DI pin state (ON; OFF).
"uAC" Voltage value
Current main power supply voltage.
"ouS" DOs Status
Current relay open closed status.
"IIII" = all relay ON (Upper bar for on, Lower bar for OFF).
"II" = DO1 ON, DO2 OFF, DO3 & DO4 NA (no bar if relay not mounted).
"IIII" = all relay OFF (Upper bar for on, Lower bar for OFF).
"rL1" Relay 1 counter
Thousands of cycles of compressor relay since manufacture.
"rL2" Relay 2 counter
Thousands of cycles of no. 2 relay since manufacture.
"rL3" Relay 3 counter
Thousands of cycles of no. 3 relay since manufacture.
"rL4" Relay 4 counter
Thousands of cycles of no. 4 relay since manufacture.
"rL5" Relay 5 counter
Thousands of cycles of no. 5 relay since manufacture.
"int" Interval Counter
Compressor run time since last defrost.
"dnt" Defrost time counter
Duration of last defrost cycle [min].
"ont" Door open counter
"ont/100"=number of door openings since last reset.
"Snu" Serial number
Serial number given at manufacturing.
"Fir" SW version
Danfoss software version number.
"HAr" HW version
Danfoss hardware version number.
"onL" OrderNoLow
Danfoss order code number.
"onH" OrderNoHigh
Danfoss order code number.
"oEL" OEM code Low
20
DKRCC.ES.RL0.F5.02 Produced by Danfoss A/S (ADAP-KOOL®) | 2016-07