| 87DKRCE.PI.RL0.F6.ML Instruction sheet | ERC 211
PORTUGUÊS
9 - Lista de pametros
Nome do parâmetro - ERC 211 Código Mín. Máx.
Uni-
dade
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Configuração cFg
Interrutor principal
-1=serviço, 0=DESLIGADO, 1=LIGADO
r12 -1 1 1 1 1 1 1 1
Aplicações pré-definidas
AP0, AP1, AP2, AP3, AP4, AP5
o61 AP0 AP5 AP0 AP1 AP2 AP3 AP4 AP5
Seleção do tipo de sensor
n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000
o06 n5 Pt1 n10 n10 n10 n10 n10 n10
Referência/Termostato r--
Setpoint de temperatura r00 -100.0 200.0 C/F 2.0 8.0 4.0 4.0 40.0 2.0
Diferencial r01 0.1 20.0 K 2.0 2.0 2.0 2.0 2.0 2.0
Limite mín. de setpoint r02 -100.0 200.0 C/F -35.0 4.0 2.0 2.0 20.0 -35.0
Limite máx. de setpoint r03 -100.0 200.0 C/F 50.0 20.0 6.0 6.0 60.0 50.0
Offset do display
(valor de correção na temperatura
apresentada)
r04 -10.0 10.0 K 0.0 0.0 0.0 0.0 0.0 0.0
Unidade do display (°C/°F) r05 -C -F -C -C -C -C -C -C
Calibração de temperatura do ar (Sair)
(offset de calibração da temperatura do ar)
r09 -20.0 20.0 K 0.0 0.0 0.0 0.0 0.0 -
Interrutor principal
-1=serviço, 0=DESLIGADO,
1=LIGADO
r12 -1 1 1 1 1 1 1 -
Definição no modo noturno
(offset de temperatura durante o
modo noturno)
r13 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0
Offset de temperatura
para o deslocamento
referencial do termostato
r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 -
Duração do pull-down r96 0 960 min 0 - 0 0 - -
Temperatura limite do pulldown r97 -100.0 200.0 C/F 0.0 - 0.0 0.0 - -
Nota: os parâmetros ocultados estão em cinza