Parameter name - ERC 211 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5
Maximum voltage
A75 0 270 V 270 270 270 270 270 270
Defrost d--
Defrost method
no=no defrost, nAt=natural
d01 no nAt no no nAt nAt no no
Defrost stop temperature d02 0.0 50.0 C/F 6.0 - - 8 - 6.0
Defrost interval
d03 0 240 hours 8 - 6 6 - 8
Max defrost time d04 0 480 min 30 - 45 60 - 30
Defrost delay at power up 
(or DI signal)
d05 0 240.0 min 0 - 0 0 - -
Drip delay d06 0 60 min 0 - 0 0 - -
Defrost stop sensor 
configuration non=time, 
Air=Sair (air temperature)
d10 non Air non - non Air - non
Compressor accumulated 
runtime to start defrost 
0=OFF
d18 0 96 hours 0 - 0 0 - -
Defrost delay after pull-down 
0=OFF
d30 0 960 min 0 - 0 0 - -
Compressor c--
Compressor minimum ON time
C01 0 30 min 0 0 0 0 0 0.0
Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2.0
Compressor OFF delay 
at door open
C04 0 15 min 0 0 0 0 0 1
Zero crossing selection C70 no yES yES yES yES yES yES YES
Others o--
Delay of outputs 
at startup
o01 0 600 min 5 5 5 5 5 5
DI1 conguration 
oFF=not used, 
Sdc=status display output, 
doo=door alarm with resumption, 
doA=door alarm without resumption, 
SCH = main switch, nig=day/ night 
mode, rFd=reference displacement, 
EAL=external alarm, dEF=defrost, 
Pud=pull-down, 
Sc=condenser sensor
o02 oFF Sc oFF oFF oFF oFF oFF oFF
Serial address o03 0 247 0 0 0 0 0 -
Password
o05 no 999 no no no no no no
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K, 
Ptc=PTC, Pt1=Pt1000
o06 n5 Pt1 n10 n10 n10 n10 n10 -
Cooling/heating 
rE=refrigeration (cooling)
Ht=heating
o07 rE Ht rE rE rE rE Ht (rE)
Display resolution 
0.1=steps of 0.1 °C 
0.5=steps of 0.5 °C, 
1.0=steps of 1.0 °C 
o15 0.1 1.0 0.1 0.1 0.1 0.1 0.1 0.1
Note: hidden parameters are greyed out