| 17DKRCE.PI.RL0.G7.ML
Installation Guide | ERC 213
Parameter Name - ERC 213 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Defrost stop sensor
configuration
non=time,
Air=Sair (air temperature),
dEF=S5 (defrost sensor)
d10 non dEF non non non non dEF dEF non
Compressor accumulated
runtime to start defrost,
0=OFF
d18 0 96 hours 0 0 0 0 0 0 -
Defrost on demand
20.0=OFF
d19 0.0 20.0 K 20.0 - - - 20.0 20.0 -
Defrost delay after pull-down
0=OFF
d30 0 960 min 0 0 0 0 0 0 -
Fan control F--
Fan at compressor cutout
FFc=fan follow compressor,
FAo=fan always ON,
FPL= fan pulsating
F01 FFc FPL FAo FAo FAo FAo FAo FAo FAo
Fan stop evaporator temperature
50.0=OFF
F04 -50.0 50.0 C/F 50.0 - - - 50.0 50.0 -
Fan ON cycle F07 0 15 min 2 2 2 2 2 2 2
Fan OFF cycle F08 0 15.0 min 2 2 2 2 2 2 2
Compressor c--
Compressor minimum ON time C01 0 30 min 0 0 0 0 0 0 0
Compressor minimum OFF time C02 0 30 min 2 2 2 2 2 2 2
Compressor OFF delay
at door open
C04 0 15 min 0 0 0 0 0 0 1
Zero crossing selection C70 no yES yES yES yES yES yES yES yES
Note: hidden parameters are greyed out
ENGLISH