| 19DKRCE.PI.RL0.G7.ML
Installation Guide | ERC 213
Parameter Name - ERC 213 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Save settings as factory
WARNING: the earlier factory settings are
overwritten
o67 no yES no no no no no no -
DO2 config
dEF=defrost, ALA=alarm
o71 dEF ALA dEF ALA dEF dEF dEF dEF dEF
Display at defrost
Air=actual air temperature,
FrE=freezed temperature, -d-="-d-" is displayed
o91 Air -d- -d- -d- -d- -d- -d- -d- -d-
Polarity P--
DI1 input polarity
nc=normally closed,
no=normally open
P73 nc no no no no no no no no
DI2 input polarity
nc=normally closed,
no=normally open
P74 nc no no no no no no no no
Invert alarm relay
0=normal, 1=invert relay action
P75 0 1 0 0 - - - - -
Keyboard lock enable P76 no yES no no no no no no -
Readouts u--
Controller Status
S0=cooling ON/Heating ON,
S2=wait for compressor ON time to elapse,
S3=wait for compressor OFF time to elapse-
restart time, S4=drip OFF delay after defrost,
S10=cooling stop S11=cooling stopped by
thermostat/heating OFF, S14=defrosting state,
S15=fan delay state after defrost, S17=door
open (DI input), S20=emergency cooling,
S25=manual control of outputs,
S30=continous cycle/Pull-down,
S32=delay of outputs at power up
u00 S0 S32 --
Air temperature (Sair) u01 -100.0 200.0 C/F ---
Read the present regulation reference u02 -100.0 200.0 C/F ---
Defrost temperature (S5) u09 -100.0 200.0 C/F --- - - -
Note: hidden parameters are greyed out