| 16 DKRCE.PI.RL0.H7.MLInstallation Guide | ERC 214
Parameter name - ERC 214 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Alarm A--
Delay for temperature alarm
during normal conditions
A03 0 240 min 30 45 30 30 30 30 30
Delay for temperature alarm
during pull-down/start-up/defrost
A12 0 240 min 60 90 60 60 60 60 60
High temperature alarm limit
(Cabinet/Room)
A13 -100.0 200.0 C/F 8.0 10.0 8.0 -15.0 8.0 -15.0 8.0
Low temperature alarm limit A14 -100.0 200.0 C/F -30.0 0.0 -2.0 -30.0 -2.0 -30.0 -30.0
DI1 delay
(time delay for selected DI1 function)
A27 0 240 min 30 30 30 30 30 30 30
DI2 delay
(time delay for selected DI2 function)
A28 0 240 min 30 30 30 30 30 30 30
Condenser high alarm limit A37 0 200 C/F 80 80 80 80 80 80 -
Condenser high block limit A54 0 200 C/F 85 85 85 85 85 85 -
Voltage protection enable A72 no yES no no no no no no no
Minimum cut-in voltage A73 0 270 V 0 0 0 0 0 0 0
Minimum cut-out voltage A74 0 270 V 0 0 0 0 0 0 0
Maximum voltage A75 0 270 V 270 270 270 270 270 270 270
Defrost d--
Defrost method
no=no defrost, nAt=natural,
EL=electrical, gAS=hot gas
d01 no gAS EL nAt EL EL EL EL EL
Defrost stop temperature d02 0.0 50.0 C/F 6.0 - - - 6.0 6.0 6.0
Defrost interval d03 0 240 hours 8 6 8 12 8 12 8
Max defrost time d04 0 480 min 30 45 15 15 30 30 30
Defrost delay at power up
(or DI signal)
d05 0 240.0 min 0 0 0 0 0 0 -
Drip delay d06 0 60 min 0 0 0 0 0 0 5
Fan delay after defrost d07 0 60 min 0 0 0 0 0 0 5
Fan start temperature
after defrost
d08 -50.0 0.0 C/F -5.0 - - - -5.0 -5.0 -
Fan during defrost d09 oFF on on on on on on on on
Note: hidden parameters are greyed out