| 15DKRCE.PI.RL0.H7.ML Installation Guide | ERC 214
9 - Parameter List
Parameter name - ERC 214 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Configuration cFg
Main switch
-1=service, 0=OFF, 1=ON
r12 -1 1 1 1 1 1 1 1 1
Predefined applications
AP0, AP1, AP2, AP3, AP4, AP5, AP6
o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 AP6
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K,
Ptc=PTC, Pt1=Pt1000
o06 n5 Pt1 n10 n10 n10 n10 n10 n10 n10
DO4 configuration
Lig=light, ALA=alarm
o36 Lig ALA Lig Lig Lig Lig Lig Lig Lig
Reference/thermostat r--
Temperature setpoint r00 -100.0 200.0 C/F 2.0 4.0 2.0 -24.0 2.0 -24.0 2.0
Differential r01 0.1 20.0 K 2.0 2.0 2.0 2.0 2.0 2.0 2.0
Min set point limitation r02 -100.0 200.0 C/F -35.0 2.0 0.0 -26.0 0.0 -26.0 -35.0
Max set point limitation r03 -100.0 200.0 C/F 50.0 6.0 4.0 -20.0 4.0 -20.0 50.0
Display offset
(correction value in display temperature)
r04 -10.0 10.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Display Unit (°C/°F) r05 -C -F -C -C -C -C -C -C -C
Calibration of Sair
(offset for air temperature calibration)
r09 -20.0 20.0 K 0.0 0.0 0.0 0.0 0.0 0.0 -
Main switch
-1=service, 0=OFF, 1=ON
r12 -1 1 1 1 1 1 1 1 -
Night set back
(offset temperature during night mode)
r13 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Thermostat reference displacement
(offset temperature)
r40 -50.0 50.0 K 0.0 0.0 0.0 0.0 0.0 0.0 -
Pull-down duration r96 0 960 min 0 0 0 0 0 0 -
Pull-down limit temperature r97 -100.0 200.0 C/F 0.0 0.0 0.0 0.0 0.0 0.0 -
Note: hidden parameters are greyed out