| 14 DKRCE.PI.RL0.H7.MLInstallation Guide | ERC 214
ENGLISH
8 - Predefined Application Setup
App Mode Description Temp. Def. type Def. end
App 0 Cooling None (no preset application)
App 1 Cooling
Medium temperature ventilated refrigeration units with timed
natural defrost
(2 – 6 °C) Natural Time
App 2 Cooling
Medium temperature ventilated refrigeration units with timed
electrical defrost
(0 – 4 °C) Electrical Time
App 3 Cooling
Low temperature ventilated refrigeration units with timed
electrical defrost
(-26 – -20 °C) Electrical Time
App 4 Cooling
Medium temperature ventilated refrigeration units with
electrical defrost (by temperature)
(0 – 4 °C) Electrical Temperature
App 5 Cooling
Low temperature ventilated refrigeration units with electrical
defrost (by temperature)
(-26 – -20 °C) Electrical Temperature
App 6 Cooling None (no preset application) with simplified parameter list
SairDI1DI2 SairDI1DI2 SairDI1DI2 S5
APP 1APP 2/3 APP 4/5
DO1
230
V AC
DO3DO4 DO1
230
V AC
DO3DO2DO4 DO1
230
V AC
DO3DO
2D
O4