| 13DKRCE.PI.RL0.H7.ML Installation Guide | ERC 214
FEATURES DESCRIPTION
Output
DO2 Defrost relay:
8 A, 2 FLA / 12 LRA, UL60730-1
8 A, 2 (2 A), EN60730-1
DO3 Fan relay:
3 A, 2 FLA/12 LRA, UL60730-1
3 A, 2 (2 A), EN60730-1
DO4 Alarm/Light relay:
2 A
Display LED display, 3 digits, decimal point and multi-function icons, °C+°F scale
Operating conditions -10 – 55 °C (14 – 131 °F), 90% Rh
Storage conditions -40 – 70 °C (-40 – 158 °F), 90% Rh
Protection
Front : IP65 (Gasket integrated)
Rear: IP00
Environmental Pollution degree II, non-condensing
Overvoltage category
II - 230 V supply version - (ENEC, UL recognized)
III - 115 V supply version - (UL recognized)
Resistance to heat and fire
Category D (UL94-V0)
Temperature for ball pressure test statement According to Annex G”
(EN 60730-1)
EMC category Category I
Approvals
UL recognition (US & Canada) (UL 60730-1)
ENEC (EN 60730-1)
CQC
CE (LVD & EMC Directive)
EAC (GHOST)
NSF
ROHS2.0
HACCP temperature monitoring in compliance with EN134785 Class I,
when used with AKS 12 sensor