| 19DKRCE.PI.RL0.H7.ML Installation Guide | ERC 214
Parameter name - ERC 214 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Display at defrost
Air=actual air temperature, FrE=freezed
temperature, -d-="-d-" is displayed
o91 Air -d- -d- -d- -d- -d- -d- -d- -d-
Polarity P--
DI1 input polarity
nc=normally closed,
no=normally open
P73 nc no no no no no no no no
DI2 input polarity
nc=normally closed,
no=normally open
P74 nc no no no no no no no no
Invert alarm relay
0=normal, 1=invert relay action
P75 0 1 0 0 0 0 0 0 -
Keyboard lock enable P76 no yES no no no no no no -
Readouts u--
Controller status
S0=cooling ON/Heating ON,
S2=wait for compressor ON time to elapse,
S3=wait for compressor OFF time to elapse-
restart time, S4=drip OFF delay after defrost,
S10=cooling stop S11=cooling stopped by
thermostat/heating OFF, S14=defrosting state,
S15=fan delay state after defrost, S17=door
open (DI input), S20=emergency cooling,
S25=manual control of outputs, S30=continous
cycle/Pull-down, S32=delay of outputs at
power up
u00 S0 S32 --
Note: hidden parameters are greyed out
ENGLISH