| 7DKRCE.PI.RL0.H7.ML Installation Guide | ERC 214
Quick Configuration at Power Up
y STEP 4: Select sensor type “o06”
The display automatically shows sensor selection parameter “o06”.
Press SET to select the sensor type.
The display shows the default value (eg. “n10” flashing).
Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to
confirm.
NOTE: All sensors must be the same type.
y STEP 5: Configure DO4 output “o36”
The display automatically shows the “o36” parameter to configure “DO4” output.
Select light (“Lig”) or alarm (“ALA”) as per the application and press SET to confirm.
The display returns to normal display mode and the control is started.