| 7DKRCE.PI.RL0.H7.ML Installation Guide | ERC 214
Quick Conguration at Power Up
y STEP 4: Select sensor type o06
The display automatically shows sensor selection parameter o06”.
Press SET to select the sensor type.
The display shows the default value (eg. n10 flashing).
Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to
confirm.
NOTE: All sensors must be the same type.
y STEP 5: Configure DO4 output o36
The display automatically shows the o36 parameter to configure DO4 output.
Select light (“Lig”) or alarm (“ALA”) as per the application and press SET to confirm.
The display returns to normal display mode and the control is started.
ENGLISH