5.4|  Quick Configuration via “cFg” menu
 – Press SET for three seconds to access the parameters groups.
 – Select “CFg” menu and press SET to enter. The first menu “r12” (main switch) is displayed.
 – Switch OFF main switch (r12=0) for changing the pre-installed application.
 – Press UP/DOWN to scroll through the parameter list.
 – Configure the “o61” parameter to select a pre-installed application:
 – Press SET to access the “o61” parameter.
 – Press UP/DOWN to select an application.
 – Press SET to confirm, “o61” is displayed.
 – Continue to set the next parameters (“o06” sensor type and “o36” DO4 configuration) in the “cFg” menu.
5.5|  Adjust set point temperature
(short press) SET: adjust setpoint temperature.
UP/DOWN: change the temperature setpoint (in setting mode the setpoint flashes).
SET: save the temperature setpoint.
5.6|  Initiate a manual defrost
DEFROST: press for 3 seconds to initiate a defsost.
The DEFROST icon is shown during defrost.
DEFROST: press for 3 seconds to stop manual defrost.
5.7|  Initiate a pull down
PULL DOWN: press for 3 seconds to stop pull down.
PULL DOWN: press for 3 seconds to initiate pull down.
“Pud”: is shown for 3 seconds to indicate pull down.
The PULL DOWN icon is flashing during pull down.
5.8|  View active alarm
Temperature and alarm codes
alternate flashes until the alarm
resolves. The alarm bell is shown
5.9|  Unlock keyboard
- After 5 minutes of no activity, the keypad is locked (if P76=yes).
- When the keypad is locked any button press shows “LoC” in the display.
- Press UP and DOWN button simultaneously for 3 seconds
  to unlock the keyboard. “unl” is displayed for 3 seconds.