1.5 Reassembly Guidelines
1.5.1 Installing Current Sensors and Busbars
Install the current sensors and busbars using the following steps.
1. Secure the current sensor brackets to the terminal mounting plate with 6 nuts (M4), 2 in each bracket.
2. Position the 3 current sensors with the arrow on each sensor facing away from the fan housing. See Illustration 1.8.
3. Secure the 6 screws (M4) that connect the current sensors to the brackets, 2 in the base of each sensor.
4. Secure the 3 retaining nuts (M10), 1 in the base of each output terminal busbar.
5. Place the terminal label back in its original position.
1 Current sensor bracket 6 Heat sink cable connector
2 Nut (M4) 7 Current sensor cables
3 Output terminal busbar 8 Current sensor cable connector
4 Current sensor bracket 9 Current sensor
5 Nut (M4) 10 Output terminal busbar retaining nut (M10)
Illustration 1.8 Current Sensors and Busbars
Installation Instructions
500 A Current Sensor Kit for
E1/E2 Enclosure Sizes
VLT
®
FC 102, FC 103, FC 202, FC 302
MI92Q102 Danfoss A/S © 10/2016 All rights reserved.