Questions and Answers

  • C
    coxvickiAug 10, 2025
    Why won't my Danfoss VLT FC 100 motor run?
    • V
      Victoria CastilloAug 10, 2025
      The motor might not run for several reasons. First, ensure the unit is powered up and shows no warnings or alarms. Check if terminal 27 is logic '1'. Make sure the [Off] key hasn't been pressed; if it has, press the [Auto On] or [Hand On] key. Also, verify that a start command is present at terminal 18. Incorrect control logic or an incorrectly programmed adjustable frequency drive may also be the cause.
  • C
    Christy LawrenceAug 15, 2025
    What to do if my Danfoss DC Drives motor is operating incorrectly?
    • L
      Luke GrantAug 15, 2025
      If your motor isn't operating correctly, there are several things to check. First, ensure the unit is programmed correctly for the reference signal and that all reference limits are set correctly. Verify the settings of all motor parameters, including compensation settings. Also, check all brake parameters and the ramp-down time. Ensure that the adjustable frequency drive is providing correct output, and there is no open winding in the motor or open phase in connection to the motor.
  • J
    James WilsonAug 19, 2025
    What to do if my Danfoss VLT FC 100 display is intermittent?
    • E
      ericjohnsonAug 19, 2025
      An intermittent display could be due to an overloaded power supply (SMPS). Try disconnecting all control wiring from the control terminal blocks. If the display stays lit, the problem is in the external control wiring. If it continues to cut out, follow the procedure for 'No Display'. Improper control wiring, overload of the 24 V output, or a fault within the adjustable frequency drive itself could also cause this overload.
  • R
    Robert DudleyAug 26, 2025
    What causes overload of digital output terminal 27 in Danfoss VLT FC 100 DC Drives?
    • J
      jacqueline32Aug 26, 2025
      An overload of digital output terminal 27 is caused by the load connected to it being too high. Check the load connected to digital output terminal 27 or remove the short-circuit connection.
  • S
    Susan WrightAug 30, 2025
    How to fix a Danfoss DC Drives with no display?
    • M
      marklynchAug 30, 2025
      If the green power-on LED is illuminated but the backlit display is dark, it indicates that the LCP is defective and must be replaced.
  • D
    David HorneSep 3, 2025
    Why is the power card supply out of range in my Danfoss VLT FC 100?
    • M
      Mark CampbellSep 4, 2025
      The supply on the power card may be out of range due to a defective power card. Check for a defective power card.