1.4.5 Removing Current Sensors and Busbars
Remove the current sensor and busbars using the following procedure. Refer to Illustration 1.7.
1. Remove the terminal label.
2. Remove the 3 retaining nuts (M10), 1 from each output terminal busbar.
3. Remove the 6 screws (M4) that connect the current sensors to the base plate, 2 from each sensor.
4. Lift the 3 current sensors and busbars from the unit.
1 Current sensor 4 Output terminal busbar
2 IGBT busbar retaining nut 5 Output terminal busbar retaining nut (M10)
3 Current sensor base plate screw (M4) 6 Terminal label
Illustration 1.7 Current Sensors and Busbars
Installation Instructions
500 A Current Sensor Kit for
E1/E2 Enclosure Sizes
VLT
®
FC 102, FC 103, FC 202, FC 302
8
Danfoss A/S © 10/2016 All rights reserved. MI92Q102