1.4.4 Removing the Current Sensor Wire Harness
Remove the current sensor wire harness using the following procedure. Refer to Illustration 1.6.
1. Disconnect the following items from the power card:
1a Unplug the 16-pin cable from the MK102 connector.
1b Detach the heat sink cable from its 3-pin connector.
1c Remove the screw (M5) attaching the ring terminal ground.
2. Detach the opposite end of the heat sink cable.
3. Detach the cable from the 3-pin connector on the high-frequency card.
4. Disconnect the wires from each of the 3 current sensors.
5. Detach any cable ties that secure the wire harness in the unit.
6. Remove the current sensor wire harness from the unit.
1 Power card 3 Heat sink cable 3-pin connector
2 16-pin cable connector (MK102) 4 Ring terminal ground (M5)
Illustration 1.6 Power Card
Installation Instructions
500 A Current Sensor Kit for
E1/E2 Enclosure Sizes
VLT
®
FC 102, FC 103, FC 202, FC 302
MI92Q102 Danfoss A/S © 10/2016 All rights reserved.
7