EasyManuals Logo

Danfoss FCM 300 Series User Manual

Danfoss FCM 300 Series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
FCM 300 Series
MG.03.B6.02 - VLT is a registered Danfoss trademark36
Function/settingsFunction/settings
Function/settingsFunction/settings
Function/settings
Key (Start)Key (Start)
Key (Start)Key (Start)
Key (Start)
Key (Start)Key (Start)
Key (Start)Key (Start)
Key (Start)
Key (Stop)Key (Stop)
Key (Stop)Key (Stop)
Key (Stop)
Default - Dual speed operationDefault - Dual speed operation
Default - Dual speed operationDefault - Dual speed operation
Default - Dual speed operation Run on set Run on Stop (and
(connect purple wire):(connect purple wire):
(connect purple wire):(connect purple wire):
(connect purple wire): reference 10 Hz** reset* - if trip)
No changes to factory setting. (+/-) jog speed
Function 2 - Dual mode operationFunction 2 - Dual mode operation
Function 2 - Dual mode operationFunction 2 - Dual mode operation
Function 2 - Dual mode operation
(connect purple wire):(connect purple wire):
(connect purple wire):(connect purple wire):
(connect purple wire): Run with Run with Stop (and
Select desired modes of operation Setup 1 Setup 2 reset* - if trip)
in Setups 1 and 2 (use para. 4-6)
Parameter 335 = 18 (select Setup)
Function 3 - Dual direction operationFunction 3 - Dual direction operation
Function 3 - Dual direction operationFunction 3 - Dual direction operation
Function 3 - Dual direction operation
(connect grey wire):(connect grey wire):
(connect grey wire):(connect grey wire):
(connect grey wire): Run Run Stop (and
Parameter 335 = 10 (start reversing) forward reverse reset* - if trip)
Parameter 200 = 1 (both directions)
*If no reset is required,
do not connect the brown wire
**or set parameter 213
At power up the unit will always be in stop mode.
Set reference will be stored during power down. If
permanent start mode is desired, connect terminal
6 to terminal 4 and do not connect purple/grey
wire to terminal 4. This means the stop function on
LOP is disabled.
NB!NB!
NB!NB!
NB!
After fitting, cut off or isolate excess wire.
Local Control
Use the +/- keys to set reference
Colour of wireColour of wire
Colour of wireColour of wire
Colour of wire
TT
TT
T
erminalerminal
erminalerminal
erminal
FunctionFunction
FunctionFunction
Function
White 2 Reference
Brown 3 Reset
Purple or Grey 4 See table under button
Green 5 See table under button
Red 6 +24V
Yellow 7 +10V
Blue 8 Ground
WW
WW
W
iringiring
iringiring
iring
Local Operation Pad (LOP)
Remote mounting kit cont.
Panel
door
Control unit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FCM 300 Series and is the answer not in the manual?

Danfoss FCM 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelFCM 300 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals