EasyManuals Logo

Danfoss IPS 8 Startup Guide

Danfoss IPS 8
17 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
User Guide | Intelligent Purging System (IPS 8) Ammonia
3 | BC437120335698en-000101 © Danfoss | Climate Solutions | 2023.07
Mechanical / Refrigeration
check
Electrical check
1) Verify that IPS 8 purger is installed, wired, and piped as per Danfoss instructions
2 )Horizontal alignment requirements must be within 2 degrees to IPS top cover. See Fig. 1
3 )The purger unit should be always kept in an upright position - from receipt to nal
installation, including possible lift to a high nal location. See Fig. 2
4) Leave space around IPS for air circulation ow. Do not install it right up to a wall. See Fig. 3
5) Inspection of possible dirt in gas lines. See Fig. 4
a. For purge point connect gas line a slope towards the IPS8 purger, must be observed.
b. No liquid traps
6) Remember to remove rubber plug. See Fig. 5.
7) Carry out proper vacuum on the purge point connect gas line and R717 side of IPS 8 purger.
The R717 side of IPS 8 purger must be pressurized prior to the IPS 8 being put into operation.
8) Before connecting power supply to IPS let it stand upright for min. 6 hours after it has been
placed at its nal location
9) After mechanical installation, but before connecting power supply IPS, please check:
a. If Danfoss drain valve used (Type SV or ICF with ICFD), then check:
b. SV: See Fig. 6a
i. Check throttle valve A is opened, and SV is properly assembled.
ii. Check that port B is closed by bolt.
c. ICFD: See Fig. 6b
i. Check stop valves
ii. Check coil is installed on solenoids (Solenoid for ICF w/ICFD (DO6) – if used)
10) Open stop valves D, as we have vacuumized the pipes before. Open manually one of purge
point solenoids E. See Fig. 6a and 6b
For general mechanical installation guidance/practice. See Fig. 6c
11) Check Main power supply. See Fig. 7
a. 084H5001, IPS 8: 230 V, AC 50 Hz
b. 084H5002, IPS 8: 230 V, AC 60 Hz
c. Power to be connected to Main switch: QS1 and Terminal: XT0
i. Terminals on QS1
1. 3, L2 – Line phase
2. 1, L1 – Neutral
ii. Terminal XT0
1. PE – Earth
12) Check connections to eld connected Purge point solenoids and ICFD solenoid (if used)
See Fig. 8a and 8b
a. Coils voltage. Same as Main power supply. No further action needed.
b. At dierent voltage for eld connected solenoids coils. See Fig. 9

Other manuals for Danfoss IPS 8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss IPS 8 and is the answer not in the manual?

Danfoss IPS 8 Specifications

General IconGeneral
BrandDanfoss
ModelIPS 8
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals