Items Supplied
See Illustration 1.1 for the list of supplied items.
1 M25 nut 5 Pressure Transmitter Unit PTU 025
2 M25 ground washer connection 6 Tube relief plate
3 M25 star washer 7 Interface cable for the C-option port
4 M25 gasket 8 Cable binders
Table 1.1
Illustration 1.1 Pressure Transmitter Unit PTU 025 and Items Supplied
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT
®
HVAC Drive FC 102
Danfoss A/S © 12/2017 All rights reserved. MI08A102

Questions and Answers

  • M
    Megan HowellAug 20, 2025
    What to do if I get Alarm 68, Safe Stop on my Danfoss Controller?
    • S
      Shawn RichardsonAug 20, 2025
      To resume normal operation of the Danfoss Controller after Alarm 68 (Safe Stop), apply 24 V DC to terminal 37 and then send a reset signal. This can be done via bus, digital I/O, or by pressing the Reset button.
  • S
    Sandra DavisAug 22, 2025
    What to do if Danfoss PTU 025 DC Drives power off?
    • S
      Sean ReyesAug 22, 2025
      If your Danfoss DC Drives show 'Power Off', it could be due to either no power supply or no link on the corresponding port. Ensure that the power is on and the link is active.
  • C
    Christy BartonAug 25, 2025
    Why Danfoss PTU 025 DC Drives power on with red light?
    • J
      Jacob SmithAug 25, 2025
      If your Danfoss DC Drives show 'Power On' and the indicator is red, this typically indicates an IP Address Conflict. Resolve the IP conflict.
  • V
    Vanessa JohnsonAug 26, 2025
    What to do if Danfoss Control Unit is in operation but not responding to control commands?
    • E
      Eric MartinezAug 26, 2025
      If the Danfoss Control Unit is running but ignoring control commands, try using the [Hand On] control or reference values from the LCP.
  • L
    leblancanthonyAug 28, 2025
    How to fix Danfoss Control Unit that does not react to any control signal?
    • K
      Kayla PhillipsAug 28, 2025
      If the Danfoss Control Unit isn't responding to any control signals, try pressing either the [Auto On] or [Hand On] button.
  • B
    Billy WelchAug 30, 2025
    What to do if Danfoss DC Drives show DC Overvoltage warning?
    • B
      barrythomasAug 30, 2025
      If your Danfoss DC Drives unit displays a DC Overvoltage warning or alarm, it means the DC-link voltage has exceeded its limit, potentially causing the drive to trip. To resolve this, consider these steps: * Connect a brake resistor. * Extend the ramp time. * Change the ramp type. * Activate the functions in parameter 2-10 Brake Function. * Increase parameter 14-26 Trip Delay at Inverter Fault. If the issue arises during a power sag, explore using kinetic back-up (parameter 14-10 Mains Failure).
  • K
    Keith LewisSep 1, 2025
    What to do if Danfoss PTU 025 display Inverter Overload warning?
    • N
      Nicole CisnerosSep 1, 2025
      If your Danfoss DC Drives unit is showing an inverter overload warning or alarm, it means the drive has been running with more than 100% overload for an extended period and is at risk of shutting down. Here's what you can do: * Compare the output current displayed on the LCP with the drive's rated current. * Compare the output current on the LCP with the measured motor current. * Monitor the thermal drive load on the LCP. If running above the drive's continuous current rating, the counter increases; if running below, it decreases.
  • H
    hannamichaelSep 3, 2025
    What to do if Danfoss PTU 025 show Mains Phase Loss alarm?
    • A
      Arthur SmallSep 3, 2025
      If your Danfoss DC Drives unit is showing a Mains Phase Loss warning or alarm, it indicates a missing phase on the supply side or an excessive mains voltage imbalance. This message can also appear due to a fault in the input rectifier. To address this, check the supply voltage and supply currents to the drive.
  • T
    Timothy ZamoraSep 7, 2025
    How to deactivate Safe Stop on Danfoss PTU 025?
    • S
      suttonmarySep 7, 2025
      If the Safe Stop is activated on your Danfoss DC Drives, it means that Safe Torque Off (STO) has been engaged. To resume normal operation, apply 24 V DC to terminal 37, and then send a reset signal via bus, digital input, or by pressing the Reset button.
  • M
    Mr. Eric Schmidt Jr.Sep 9, 2025
    What to do if Danfoss PTU 025 display Live Zero Error?
    • Z
      Zachary RobertsonSep 9, 2025
      The 'Live Zero Error' warning or alarm on your Danfoss DC Drives appears if programmed in parameter 6-01 Live Zero Timeout Function and the signal on one of the analog inputs is less than 50% of the minimum value programmed for that input. Check the connections on all analog mains terminals. Also, check control card terminals 53 and 54 for signals, using terminal 55 as common. Ensure that the drive programming and switch settings match the analog signal type.

Danfoss PTU 025 Specifications

General IconGeneral
Supply voltage24 VDC
Rated current25 A
Output voltage0-24 VDC
Protection classIP20
Control signal0-10 V, 4-20 mA
Protectionovertemperature