Items Supplied
See Illustration 1.1 for the list of supplied items.
1 M25 nut 5 Pressure Transmitter Unit PTU 025
2 M25 ground washer connection 6 Tube relief plate
3 M25 star washer 7 Interface cable for the C-option port
4 M25 gasket 8 Cable binders
Table 1.1
Illustration 1.1 Pressure Transmitter Unit PTU 025 and Items Supplied
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT
®
HVAC Drive FC 102
Danfoss A/S © 12/2017 All rights reserved. MI08A102

Questions and Answers

  • D
    david82Sep 12, 2025
    Why Danfoss PTU 025 DC Drives shows Option Module Configuration has Changed alarm?
    • A
      Andrea GravesSep 12, 2025
      If your Danfoss DC Drives displays an alarm indicating that the Option Module Configuration has changed, it means that options have been added or removed since the last power-down. To resolve this, verify that the configuration change was intentional, and then reset the unit.
  • C
    Cynthia AtkinsSep 13, 2025
    How to fix Heat Sink Temperature Low warning on Danfoss PTU 025 DC Drives?
    • M
      Mandy WoodSep 13, 2025
      If your Danfoss DC Drives unit shows a Heat Sink Temperature Low warning, it means the drive is too cold to operate, based on the temperature sensor in the IGBT module. To resolve this, increase the ambient temperature of the unit. Alternatively, supply a trickle amount of current to the drive whenever the motor is stopped by setting parameter 2-00 DC Hold/Preheat Current to 5% and parameter 1-80 Function at Stop.
  • B
    Bradley LynchSep 15, 2025
    What to do if Danfoss DC Drives displays 10 Volts Low warning?
    • A
      Alexis FoxSep 15, 2025
      If your Danfoss DC Drives unit displays a '10 Volts Low' warning, it means the control card voltage from terminal 50 is less than 10 V. To troubleshoot, first remove the wiring from terminal 50. If the warning clears, the issue lies with the wiring. If the warning persists, replace the control card.
  • U
    ubautistaSep 17, 2025
    What causes 24 V Supply Low warning on Danfoss PTU 025?
    • A
      Andrea SandersSep 18, 2025
      If your Danfoss DC Drives unit is showing a '24 V Supply Low' warning, it indicates that the supply on the power card is out of range. To fix this, check for a defective power card.