EasyManuals Logo

Danfoss PTU 025 Programming Guide

Danfoss PTU 025
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #210 background imageLoading...
Page #210 background image
3.25 Parameters: 30-** Special Features
30-22 Locked Rotor Protection
Available for PM motors only, in VVC
+
open-loop mode.
Option: Function:
[0] O
[1] On Protects the motor from the locked rotor condition. The
control algorithm detects a possible locked rotor
condition in motor and trips the frequency converter to
protect the motor.
30-23 Locked Rotor Detection Time [s]
Available for PM motors only, in ux sensorless-mode and VVC
+
open-loop mode.
Range: Function:
Size related* [0.05 - 1 s] Time period for detecting the locked
rotor condition. A low parameter
value leads to faster detection.
Parameter Descriptions
VLT
®
HVAC Drive FC 102
208 Danfoss A/S © 03/2015 All rights reserved. MG11CE02
33

Table of Contents

Other manuals for Danfoss PTU 025

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss PTU 025 and is the answer not in the manual?

Danfoss PTU 025 Specifications

General IconGeneral
BrandDanfoss
ModelPTU 025
CategoryDC Drives
LanguageEnglish

Related product manuals