3-95 Ramp Delay
Range: Function:
Size
related*
[ 0.000 -
0.000 ]
Enter the delay required from activation of
the digital potentiometer function until the
frequency converter starts to ramp the
reference. With a delay of 0 ms, the
reference starts to ramp as soon as
increase/decrease is activated. See also
parameter 3-91 Ramp Time.
Speed
Time (s)
Inc
130BA158.11
P 3-95
Illustration 3.22 Ramp Delay Case 1
Speed
Time (s)
Dec
Inc
130BA159.11
P 3-95
Illustration 3.23 Ramp Delay Case 2
Parameter Descriptions
VLT
®
HVAC Drive FC 102
64 Danfoss A/S © 03/2015 All rights reserved. MG11CE02