1 x
Energy meter
2 x
Gaskets
1 x
Temperature sensor
O-ring and mounting pin
4 x
Wired seals
1 x
Installation
& User Guide
Note!
• For cooling meters a wall mounting kit is delivered with the product
2. Installation
2.1 Preparation
SonoSelect incorporates a tamper monitor-
ing function. If the calculator is opened the
meter will set alarm E13 in display.
Don’t open unless for adding communica-
tion module, replacing battery or installing
cables.
Reset requires Bluetooth dongle 014U1963
and SonoApp service tool.
SonoSelect is delivered with the option
of reconfiguring supply/return using the
Bluetooth dongle 014U1963 and SonoApp
service tool.
Note!
• Product is approved for ambient temperature between 5-55 °C, non-condensing (indoor installation). It is
recommended to install Calculator at max. 45 °C to secure optimal conditions for battery lifetime. At media
temperatures below ambient temperature (cooling) the calculator must be mounted separately from the flow
sensor to prevent condensation.
• Avoid installation stress from pipes and fittings.
• Flush the system.