EasyManua.ls Logo

Danfoss SonoSafe - 1 General; Inside the Box; 2 Installation; Preparation

Danfoss SonoSafe
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 | © Danfoss | Energy Meters | 2018.01 VUIGB802
Installation & User Guide SonoSelect and SonoSafe
1. General
Ambient operating temperature class A 5 - 55 °C (Indoor installation, non-condensing)
Ambient storage temperature -25 - 60 °C
Temperature media 5 - 95 °C
Mechanical environment class M2
Electromagnetic environment class E1
Pressure PN16
MID Accuracy Class 2
1.1 Inside the box
Description of components included in the box
107/2015 © Danfoss VDIGH102
Installation Guide
SonoSelect and SonoSafe
energy meters
1 x
Energy meter
2 x Gaskets &
1 temperature
sensor O-ring
4 x
Wired seals
1 x
Installation
& User Guide
Note: For cooling meters a wall mounting kit is delivered with the product
2. Installation
2.1 Preparation
SonoSelect incorporates a tamper monitoring function. If the
calculator is opened the meter will set alarm E13 in display.
Don’t open unless for adding communication module,
replacing battery or installing cables.
Reset requires Bluetooth dongle 014U1963 and SonoApp
service tool.
SonoSelect is delivered with the option of reconfiguring
supply/return using the Bluetooth dongle 014U1963 and
SonoApp service tool.
Note:
Product is approved for ambient temperature between 5-55 °C, non-condensing (indoor installation). It is recommended
to install Calculator at max. 45 °C to secure optimal conditions for battery lifetime. At media temperatures below ambient
temperature (cooling) the calculator must be mounted separately from the flow sensor to prevent condensation.
Avoid installation stress from pipes and fittings.
Flush the system.

Related product manuals