TP7001
10
GB
Option 35 - Set Integration Time
(Option 34 set to 3, 6, 9 or 12)
This adjusts the integration time of the PI algorithm to
increase control accuracy. It is only active if Option 34
has been set to Chrono 3, 6, 9 or 12. It should only be
adjusted after seeking advice from the manufacturer.
Press + until Option 35 is displayed, use V or Λ to
select required setting.
(NB Seek advice prior to adjusting)
2.5 = Integration time set to 2.5% (Factory Setting)
5 = Integration time set to 5%
10 = Integration time set to 10%
Option 36 - Set Temperature Override Rule
This establishes the degree of temperature override
available to the user. Press + until Option 36 is
displayed, use V or Λ to select required setting. This
option is not possible if the thermostat is set to STAT
in Option 40.
0 = No limit (Factory Setting)
1 = Limited to ±2ºC (±3ºF)
2 = No override allowed
Option 37 - Set Time Duration of Override Rule
This establishes the duration of a temperature
override available to the user. Press + until Option 37
is displayed, use V or Λ to select required setting. This
option is not possible if the thermostat is set to STAT
in Option 40 or Override Limit is disabled.
0 = Next Event (Factory Setting)
1 = 1 Hour
2 = 2 Hours
3 = 3 Hours
4 = 4 Hours