VL 5000 Crane
Mains Supply 400 - 500 V
According to international requirements VLT type 5042 5052 5062
Output current
I
VLT,N
(S3 60%) [A]
(400-500 V)
58 69 85
I
VLT, MAX
(60 s) [A] (400-500 V) 97.6 116.8 135
Output
S
VLT,N
(S3 60%) [kVA]
(400-500 V)
39.2
46.6 57.4
Typical shaft output P
VLT,N
[kW] 22 30 37
Typical shaft output P
VLT,N
[HP] 30 41 50
Max. cable cross-section to motor and
brake [mm
2
]/[AWG]
2)3)
IP20 50/0 50/0
Rated input current I
L,N
(S3 60%) [A] (400 V) 51 62 76
Max. cable cross-section
power[mm
2
]/[AWG]
2)3)
35/2 50/0 50/0
Max. pre-fuses [-]/UL
1)
[A] 100/100 125/125 150/50
Efficiency 0.96 0,96 0.96
Weight IP 20 SB [kg] 41 42 43
Power loss at max. load. 1004 1210 1500
Enclosure IP20 IP20 IP20
1. For type of fuse see section Fuses.
2. American wire gauge.
3. Connection stud 1 x M8/2 x M8.
MG.50.N4.02 - VLT is a registered Danfoss trademark