VL 5000 Crane
Fuses
UL compliance
380-500 V
Bussmann SIBA Littel fuse Ferraz-Shawmut
5042 KTS-R100 2028220-125 KLS-R100 A6K-100R
5052 KTS-R125 2028220-125 KLS-R125 A6K-125R
5062 KTS-R150 2028220-160 KLS-R150 A6K-150R
5072 FWH-220 2028220-200 L50S-225 A50-P225
5102 FWH-250 2028220-250 L50S-250 A50-P250
5122 FWH-300 2028220-315 L50S-300 A50-P300
5152 FWH-350 2028220-315 L50S-350 A50-P350
5202 FWH-400 206xx32-400 L50S-400 A50-P400
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drive
s.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL
compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 5001-5027 200-240 V type gG
VLT 5001-5062 380-500 V type gG
VLT 5032-5052 200-240 V type gR
VLT 5072-5500 380-500 V type gR
Not following the recommendation may result
in unnecessary damage of the drive in case of
malfunction. Fuses must be designed for protection in
a circuit capable of supplying a maximum of 100000
A
rms
(symmetrical), 500/600 V maximum.
MG.50.N4.02 - VLT is a registered Danfoss trademark