VL 5000 Crane
Programming
NB!:
Upload/download can only be performed
in stop mode. Download can o
nly be
performed to a frequency converter with
the same software version number, see parameter
626 Database identification no.
009 DISPLAY LINE 2
Value:
Reference [%] (REFERENCE [%])
[1]
Reference [unit] (REFERENCE [UNIT])
[2]
Frequency [Hz] (FREQUENCY [HZ])
[4]
Motor speed [RPM]
(MOTOR SPEED)
[5]
Motor current [A] (MOTOR CURRENT [A])
[6]
Torque [%] (TORQUE [%])
[7]
Power [kW] (POWER [KW])
[8]
Power [HP] (POWER [HP] [US])
[9]
Output energy [kWh]
(OUTPUT ENERGY [KWH])
[10]
Motor voltage [V] (MOTOR VOLTAGE [V])
[11]
DC link voltage [V] (DC LINK VOLTAGE [V])
[12]
Thermal load, motor [%]
(MOTOR THERMAL [%])
[13]
Thermal load, VLT [%] (VLT THERMAL [%])
[14]
Hours run [Hours] (RUNNING HOURS)
[15]
Digital input [Binary code]
(DIGITAL INPUT [BIN])
[16]
Analogue input 53 [V]
(ANALOG INPUT 53 [V])
[17]
Analogue input 58 [mA]
(ANALOG INPUT 58 [MA])
[18]
Analogue input 60 [mA]
(ANALOG INPUT 60 [MA])
[19]
Load estimator Max [RPM)
(LOAD EST MAX [RPM])
[20]
External reference [%] (EXTERNAL REF [%])
[21]
Status word [Hex] (STATUS WORD [HEX])
[22]
Brake effect/2 min. [KW]
(BRAKE ENERGY/2 MIN)
[23]
Brake effect/sec. [kW] (BRAKE ENERGY/S)
[24]
Heat sink temp. [°C] (HEATSINK TEMP [°C])
[25]
Alarm word [Hex] (ALARM WORD [HEX])
[26]
Control word [Hex]
(CONTROL WORD [HEX])
[27]
Warning word [Hex]
(WARNING WORD [HEX])
[28]
Function:
This parameter allows a choice of the data value
to be displayed in line 2 of the display.
Parameters 010-012 enable the use of three additional
data values to be displayed in line 1.
Description of choice:
Reference [%] corresponds to the total reference
(sum of digital/analogue/bus).
Reference [unit] gives the status value of terminals
53, 58, 60 using the unit stated on the basis of
configuration in parameter 100 (Hz, Hz and rpm).
Frequency [Hz] gives the motor frequency, ie. the
output frequency from the frequency converter.
Motor speed [RPM] corresponds to the
present motor speed.
Motor current [A] states the phase current of the
motor measured as effective value.
Torque [%] gives the current motor load in
relation to the rated motor torque.
Power [kW] states the actual power consumed
by the motor in kW.
Power [HP] states the actual power consumed
by the motor in HP.
Output energy [kWh] states the energy
consumed by the motor since the latest reset
was made in parameter 618.
Motor voltage [V] states the voltage supplied
to the motor.
DC link voltage [V] states the intermediate circuit
voltage in the frequency converter.
Thermal load, motor [%] states the
calculated/estimated thermal load on the
motor. 100% is the cut-out limit.
Thermal load, VLT [%] states the calculated/estimated
thermal load on the frequency converter.
100% is the cut-out limit.
Hours run [Hours] states the number of hours that the
motor has run since the latest reset in parameter 619.
Digital input [Binary code] states the signal states
from the 8 digital terminals (16, 17, 18, 19, 27, 29,
32 and 33) Input 16 corresponds to the bit at the far
left. 0 =nosignal,1 = connected signal.
Analogue input 53 [V] states the signal
value on terminal 53.
Analogue input 58 [mA] states the signal
value on terminal 58.
Analogue input 60 [mA] states the signal
value on terminal 60.
Load estimator Max [RPM] Displays the calculated
maximum speed from the load measurement.
External reference [%] gives the sum of the
external reference as a percentage (the sum
of analogue/pulse/bus).
= factory setting. () = display text [] = value for use in communication via serial communication port