VLT
®
8000 AQUA
All about VLT 8000
AQUA
■ Immunity, continued
Burst Surge ESD Radiated electro- Mains RF common Radiated radio
Basic standard IEC 1000-4-4 IEC 1000-4-5 1000-4-2 magnetic field distortion mode voltage freq.elect.field
IEC 1000-4-3 VDE 0160 ENV 50141 ENV 50140
Acceptance criterion B B B A A A
Port connection CM DM CM - - CM CM
Line OK OK - - - OK OK -
Motor OK --- - - OK -
Control lines OK -OK- - - OK -
PROFIBUS option OK -OK- - - OK -
Signal Interface<3 m OK --- - - - -
Enclosure - --OK OK - - OK
Load sharing OK --- - - OK -
Standard bus OK -OK- - - OK -
Basic specifications - - - -
Line 4kV/5kHz/DCN 2kV/2 4kV/12 - - 2,3 x U
N
2)
10 V
RMS
-
Motor 4kV/5kHz/CCC --- - - 10 V
RMS
-
Control lines 2kV/5kHz/CCC -2kV/2
1)
- - - 10 V
RMS
-
PROFIBUS option 2kV/5kHz/CCC -2kV/2
1)
- - - 10 V
RMS
-
Signal interface<3 m 1kV/5kHz/CCC --- - - 10 V
RMS
-
Enclosure - --8kVAD
6kVCD
10 V/m
- - -
Load sharing 4kV/5kHz/CCC --- - - 10 V
RMS
-
Standard bus 2kV/5kHz/CCC -4kV/2
1)
- - - 10 V
RMS
-
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
1
) Injection on cable shield
2
)2.3xU
N
:max.testpulse380V
AC
: Class 2/1250 V
PEAK
, 415 VAC: Class 1/1350 V
PEAK
MG.83.A2.02 - VLT is a registered Danfoss trademark
195