Operating Guide
1 Introduction
AQ435824155085en-000101 / 130R1294 | 1Danfoss A/S © 2023.06
VLT® AutomationDrive FC 360
*M0040301*
This operating guide provides necessary information for qualied personnel to install and commission the
AC drive. Read and follow the instructions to use the drive safely and professionally.
Do not dispose of equipment containing electrical components together with domestic waste.
Collect it separately in accordance with local and currently valid legislation.
Pay particular attention to the safety instructions and general warnings to avoid the risk of death, serious
injury, and equipment or property damage.
2 Safety
WARNING
HIGH VOLTAGE
AC drives contain high voltage when connected to AC mains input.
UNINTENDED START
The motor may start from control panel, I/O inputs, or eldbus at any time, when the drive is connected to the AC mains.
DISCHARGE TIME
The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be
present even when the warning indicator lights are o.
- Stop the motor, and disconnect AC mains, permanent magnet type motors.
- Wait for the capacitors to discharge fully and measure it before performing any service or repair work.
- The minimum waiting time is 20 minutes.
LEAKAGE CURRENT
Leakage currents of the drive exceed 3.5 mA. Make sure that the minimum size of the ground conductor complies with the
local safety regulations for high touch current equipment.
3.1 Mechanical Dimensions
3 Installation
130R1294
90–315 kW, Enclosure Sizes J8–J9
Test method according to IEC 60068-2-43
H
2
S (10 days)
Class 3C3
Aggressive gases (IEC 60721-3-3)
Class Kd
Aggressive environment (IEC 60068-2-43) H
2
S test
Relative humidty
5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation)
0.7 g
Vibration test (standard)
IP20/Chassis
J8–J9 enclosure size
5 Ambient Conditions
4 Specications
Table 2: Electrical Data for Normal Overload, Mains Supply 3x380–480 V AC
Table 3: Electrical Data for High Overload, Mains Supply 3x380–480 V AC
Drive
Enclosure size
Normal overload=110% current during 60 s
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460 V) [A]
Intermittent (60 s overload) (at 460 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460 V) [A]
Maximum number and size of cables per phase
Mains and motor [mm (AWG)]
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Eciency [%]
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Q110 Q132 Q160 Q200 Q250 Q315
110 132 160 200 250 315
150 200 250 300 350 450
212 260 315 395 480 588
233 286 347 435 528 647
190 240 302 361 443 535
209 264 332 397 487 589
147 180 218 274 333 407
151 191 241 288 353 426
204 251 304 381 463 567
183 231 291 348 427 516
315
2x95 (2x3/0) 2x185 (2x350 mcm)
75 (167) 80 (176)
350 400 550 630 800
2559 2954 3770 4116 5137 6674
2261 2724 3628
98
0–590
110 (230)
3569 4566 5714
J8 J8 J8 J9 J9 J9
Drive
Enclosure size
High overload=150% current during 60 s
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460 V) [A]
Intermittent (60 s overload) (at 460 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460 V) [A]
Maximum number and size of cables per phase
Mains and motor [mm (AWG)]
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Eciency [%]
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
H90K H110 H132 H160 H200 H250
90 110 132 160 200 250
125 150 200 250 300 350
177 212 260 315 395 480
266 318 390 473 593 720
160 190 240 302 361 443
240 285 360 453 542 665
123 147 180 218 274 333
127 151 191 241 288 353
171 204 251 304 381 463
154 183 231 291 348 427
315
2x95 (2x3/0) 2x185 (2x350 mcm)
75 (167) 80 (176)
350 400 550 630 800
2031 2289 2923 3093 4039 5004
1828 2051 2089
98
0–590
110 (230)
2872 3575 4458
J8 J8 J8 J9 J9 J9
Illustration 3: Connecting to Mains, Motor, Control Terminals, and Relays
Illustration 4: Control Terminals
3.3 Connecting to Mains, Motor, Control Terminals, and Relays
3.4 Control Terminals
3.2 Removing the Front Cover
Front view Side view Back view
C
b1
B
b D
A
a
E
F
G
D
Illustration 1: Mechanical Dimensions, Enclosure Sizes J8–J9
Table 1: Power Ratings, Dimensions, and Weights for Enclosure Sizes J8–J9
Enclosure size
(IP20)
Enclosure size
(IP20)
J8
J9
J8
J9
Maximum
weight
[kg (lb)]
98 (216)
164 (362)
128 (5.0)
176 (6.9)
495 (19.5)
611 (24.1)
148 (5.8)
E F G
148 (5.8)
Center of gravity [mm (in)]
250 (9.8)
350 (13.8)
180 (7.1)
280 (11.0)
200 (7.9)
B b b1
271 (10.7)
Width [mm (in)]
889 (35.0)
1096 (43.1)
909 (35.8)
1122 (44.2)
844 (33.2)
A A
(1)
a
1051 (41.4)
Height [mm (in)]
110–160 (150–250)
200–315 (300–450)
3x380–480 V
Power [kW (hp)]
11 (0.4)
11 (0.4)
D
Mounting hole [mm (in)]
375 (14.8)
375 (14.8)
C
Depth [mm (in)]
Procedure:
Step 1: Loosen and remove the 2 screws on the front cover.
Step 2: Disconnect the front cover from the hooks.
RS485 termination switch
(ON=RS485 terminated, OFF=Open)
1 2
O N
Note: (1) Including decoupling plate.
e30bv154.10
e30bv155.10e30bv159.10 e30bv161.10
RELAY 1 RELAY 2
01 02 03 04 05 06
COMMON
NO
NC
COMMON
NO
NC
VDD1
DI18
DI19
DIO27
DI31
DI32
DI33
GND
DIO29
12 18 19 27 29 31 32 33 20
10 V
AI53
AI54
AO42
AO45
GND
50 53 54 42 45 55
COM RS 485
P RS 485
N RS 485
61 68 69
Illustration 2: Removing the Front Cover
Step 1 Step 2
Screws
Hooks
Mains
Motor
Ground
Control
terminals
Relays

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?