WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors,
which can remain charged even when the frequency
converter is not powered. Failure to wait the specied
time after power has been removed before performing
service or repair work, could result in death or serious
injury.
1. Stop the Compressor.
2. Disconnect the AC mains, permanent magnet
type motors, and remote DC-link power
supplies, including battery back-ups, UPS, and
DC-link connections to other frequency
converters.
3. Wait for the capacitors to discharge fully before
performing any service or repair work. The
duration of waiting time is specied in Table 1.2.
Voltage [V] Cooling capacity [TR] Minimum waiting time
(minutes)
3x200 4–6.5 15
3x400 4–5 4
3x400 6.5 15
High voltage may be present even when the warning LED
indicator lights are o.
Table 1.2 Discharge Time
WARNING
LEAKAGE CURRENT HAZARD
Leakage currents exceed 3.5 mA. Failure to ground the
frequency converter properly can result in death or
serious injury.
Ensure the correct grounding of the equipment
by a certied electrical installer.
WARNING
EQUIPMENT HAZARD
Contact with rotating shafts and electrical equipment
can result in death or serious injury.
Ensure that only trained and qualied personnel
perform installation, start up, and maintenance.
Ensure that electrical work conforms to national
and local electrical codes.
Follow the procedures in these operating
instructions.
WARNING
UNINTENDED MOTOR ROTATION
WINDMILLING
Unintended rotation of permanent magnet motors can
result in serious injury or equipment damage.
Ensure that permanent magnet motors are
blocked to prevent unintended rotation.
CAUTION
INTERNAL FAILURE HAZARD
An internal failure in the frequency converter can result
in serious injury, when the frequency converter is not
properly closed.
Ensure that all safety covers are in place and
securely fastened before applying power.
1.5 Conventions
Numbered lists indicate procedures.
Bulleted lists indicate other information.
Italicized text indicates the following:
- Cross-reference
- Link
- Parameter name
- Parameter option
- Parameter group name
All dimensions in drawings are in mm (inch).
An asterisk (*) indicates default setting of a
parameter.
1.6
Additional Resources
VLT
®
Compressor Drive CDS 803 Operating Guide
entails information on safety, installation and how
to program. It provides a list of warnings and
alarms and general specications.
VLT
®
Compressor Drive CDS 803 Programming
Guide provides information on how to program
and includes complete parameter descriptions.
VLT
®
Compressor Drive CDS 803 Design Guide
entails all technical information about the
frequency converter and customer design and
applications.
MCT 10 Set-up Software enables the user to
congure the frequency converter from a
Windows
-based PC environment.
Supplementary publications and manuals are available
from Danfoss. See www.danfoss.com and search for
documentation.
Introduction
VLT
®
Compressor Drive CDS 803
4 Danfoss A/S © 06/2019 All rights reserved. MG18P202
11

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals