Parameter 6-25
Terminal 54
High Ref./
Feedb. Value
Enter the feedback value that corresponds to the voltage or
current set in parameter 6-21 Terminal 54 High Voltage/pa-
rameter 6-23 Terminal 54 High Current.
Parameter 6-26
Terminal 54 Fil-
ter Time Con-
stant
Enter the filter time constant.
Parameter 6-29
Terminal 54
mode
Select if terminal 54 is used for current or voltage input.
Parameter
20-81 PI Nor-
mal/Inverse
Control
Select [0] Normal to set the process control to increase the
output speed when the process error is positive. Select [1] In-
verse to reduce the output speed.
Parameter
20-83 PI Start
Speed [Hz]
Enter the motor speed to be attained as a start signal for
commencement of PI control.
Parameter
20-93 PI Propor-
tional Gain
Enter the process controller proportional gain. Quick control
is obtained at high amplification. However, if amplification is
too high, the process may become unstable.
Parameter
20-94 PI Inte-
gral Time
Enter the process controller integral time. Obtain quick con-
trol through a short integral time, though if the integral time
is too short, the process becomes unstable. An excessively
long integral time disables the integral action.
Parameter
30-22 Locked
Rotor Detection
Parameter
30-23 Locked
Rotor Detection
Time [s]
4.2.4 Motor Setup
The motor setup wizard guides users through the needed motor parameters.
Table 13: Motor Setup Wizard Settings
Parameter 0-03
Regional Set-
tings
[0] 200–240 V/50 Hz/IT-grid
[1] 200–240 V/50 Hz/Delta
[2] 200–240 V/50 Hz
[10] 380–440 V/50 Hz/IT-grid
[11] 380–440 V/50 Hz/Delta
[12] 380–440 V/50 Hz
Select the operating mode for restart after reconnection of
the drive to mains voltage after power down.
AQ367426199594en-000101 / 130R098836 | Danfoss A/S © 2021.06