A no-flow condition has been detected in the system. Pa-
rameter 22-23 No-Flow Function is set for alarm.
A dry-pump condition has been detected in the system.
Parameter 22-26 Dry Pump Function is set for alarm.
An end-of-curve condition has been detected in the sys-
tem. Parameter 22-50 End of Curve Function is set for
alarm.
Torque is below the torque level set for no load, indicat-
ing a broken belt. See parameter group 22-6* Broken Belt
Detection.
Flow/pressure
Info Missing
Sensorless-pump table is missing or wrong. Download
sensorless-pump table again.
High back EMF voltage. Stop the rotor of the PM motor.
This warning applies to PM motors only. When the back
EMF exceeds 90% x U
invmax
(overvoltage threshold) and
does not drop to normal level within 5 s, this warning is
reported. The warning remains until the back EMF returns
to a normal level.
When the drive is not in operation, a broken check valve
leads to the motor runs in reverse.
Fire mode has been activated.
Fire mode lim-
its exceeded
Fire mode has suppressed 1 or more warranty voiding
alarms.
The power or switch mode power supply has been ex-
changed (on 400 V, 30–90 kW (40–125 hp) units). Contact
the local Danfoss supplier.
The drive has a new type code (on 400 V, 30–90 kW (40–
125 hp) units). Contact the local Danfoss supplier.
5.2 LCP Errors Messages
LCP errors are not warnings or alarms. They do not affect the operation of the drive. An LCP error example on the LCP is shown in
the following illustration.
e30bu794.10
0-**: Operation / Dis
1-**: Load and Motor
Button disabled
Illustration 19: LCP Error Example