5 Warnings and Alarms
5.1 List of Warnings and Alarms
Table 14: Warnings and Alarms
Signal on terminal 53 or 54 is less than 50% of the value
set in parameter 6-10 Terminal 53 Low Voltage, parameter
6-12 Terminal 53 Low Current, parameter 6-20 Terminal 54
Low Voltage, or parameter 6-22 Terminal 54 Low Current.
See also parameter group 6-0* Analog I/O Mode.
No motor is connected to the output of the drive.
Missing phase on the supply side or too high voltage im-
balance. Check the supply voltage. See parameter 14-12
Function at Mains Imbalance.
DC-link voltage exceeds the limit.
DC-link voltage drops below voltage warning low-limit.
More than 100% load for a long time.
Motor is too hot due to more than 100% load for a long
time. See parameter 1-90 Motor Thermal Protection.
Thermistor or thermistor connection is disconnected. See
parameter 1-90 Motor Thermal Protection.
Inverter peak current limit is exceeded.
Discharge from output phases to ground.
Short circuit in motor or on motor terminals.
No communication to drive. See parameter group 8-0*
General Settings.
The heat sink cooling fan is not working (only on 400 V,
30–90 kW (40–125 hp) units).
Motor phase U is missing. Check the phase. See parameter
4-58 Missing Motor Phase Function.
Motor phase V is missing. Check the phase. See parameter
4-58 Missing Motor Phase Function.
Motor phase W is missing. Check the phase. See parame-
ter 4-58 Missing Motor Phase Function.
Contact the local Danfoss supplier.
Discharge from output phases to ground, using the value
of parameter 15-31 Alarm Log Value if possible.
Control voltage is low. Contact the local Danfoss supplier.
AQ367426199594en-000101 / 130R0988 | 41Danfoss A/S © 2021.06
Warnings and Alarms
VLT® HVAC Drive FC 131
Operating Guide