Drive
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Intermittent (3x380–440 V) [A]
38.7
53.9
64.2
69.3
81.6
113.2
136.3
Continuous (3x441–480 V) [A]
32
41.6
52
56
73.5
91
112
Intermittent (3x441–480 V) [A]
35.2
45.8
57.2
61.6
80.9
100.1
123.2
1
Applies for dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and
typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to Danfoss MyDrive® ecoSmart website.
2
Efficiency measured at nominal current. For energy efficiency class, see 6.4.13 Ambient Conditions. For part load losses, see Danfoss MyDrive®
ecoSmart website.
6.2 EMC Emission Test Results
The following test results have been obtained using a system with a drive, a shielded control cable, a control box with potentiome-
ter, and a shielded motor cable.
Table 18: EMC Emission Test Results
RFI filter
type
Conduct emission. Maximum shielded cable length [m (ft)]
Radiated emission
Industrial environment
EN 55011
Class A Group 2
Industrial environ-
ment
Class A Group 1
Industrial environ-
ment
Class B
Housing, trades and
light industries
Class A Group 1
Industrial environ-
ment
Class B
Housing, trades
and light industries
EN/IEC
61800-3
Category C3
Second environment
Industrial
Category C2
First environment
Home and office
Category C1
First environment
Home and office
Category C2
First environment
Home and office
Category C1
First environment
Home and office
Without
external
filter
With ex-
ternal
filter
Without
external
filter
With ex-
ternal
filter
Without
external
filter
With
external
filter
Without
external
filter
With
exter-
nal fil-
ter
Without
external
filter
With
exter-
nal fil-
ter
H2 RFI filter (EN 55011 A2, EN/IEC 61800-3 C3)
0.75–18.5
kW (1.0–25
hp) 3x380–
480 V IP54
25 (82)
Yes
22–90 kW
(30–120 hp)
3x380–480
V IP54
25 (82)
No
No
H3 RFI filter (EN55011 A1/B, EN/IEC 61800-3 C2/C1)
0.75–18.5
kW (1.0–25
hp) 3x380–
480 V IP54
25 (82)
10 (33)
Yes
22–90 kW
(30–120 hp)
3x380–480
V IP54
25 (82)
10 (33)
Yes