EasyManua.ls Logo

Danfoss VLT HVAC Drive FC 131 - 10 V DC Output and Ambient Conditions

Danfoss VLT HVAC Drive FC 131
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maximum terminal load (AC-1)
(1)
on 04–05 (NO) (resistive load)
(2)(3)
400 V AC, 2 A
Maximum terminal load (AC-15)
(1)
on 04–05 (NO) (inductive load
@ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 04–05 (NO) (resistive load)
80 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 04–05 (NO) (inductive load)
24 V DC, 0.1 A
Maximum terminal load (AC-1)
(1)
on 04–06 (NC) (resistive load)
240 V AC, 2 A
Maximum terminal load (AC-15)
(1)
on 04–06 (NC) (inductive load
@ cosφ 0.4)
240 V AC, 0.2 A
Maximum terminal load (DC-1)
(1)
on 04–06 (NC) (resistive load)
50 V DC, 2 A
Maximum terminal load (DC-13)
(1)
on 04–06 (NC) (inductive load)
24 V DC, 0.1 A
Minimum terminal load on 01–03 (NC), 01–02 (NO), 04–06 (NC),
04–05 (NO)
24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1
IEC 60947 parts 4 and 5. Endurance of the relay varies with different load type, switching current, ambient temperature, driving configuration,
working profile, and so forth. It is recommended to mount a snubber circuit when connecting inductive loads to the relays.
2
Overvoltage Category II.
3
UL applications 300 V AC 2 A.
6.4.12 Control Card, 10 V DC Output
Terminal number
50
Output voltage
10.5 V ±0.5 V
Maximum load
25 mA
6.4.13 Ambient Conditions
Enclosure protection rating
IP54 (not for outdoor installation)
Vibration test
1.0 g
Maximum relative humidity
5–95% (IEC 60721-3-3; Class 3K3 (non-condensing)) during opera-
tion
Aggressive environment (IEC 60721-3-3), non-coated enclosure
sizes I2–I8
Class 3C2
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
(1)
See maximum output current at 40/50 °C (104/122 °F) in 6.1.1
3x380–480 V AC.
Minimum ambient temperature during full-scale operation
0 °C (32 °F)
Minimum ambient temperature at reduced performance, enclo-
sure sizes I2–I4
-20 °C (-4 °F)
Minimum ambient temperature at reduced performance, enclo-
sure sizes I6–I8
-10 °C (14 °F)
Temperature during storage/transport
-30 to +65/70 °C (-22 to +149/158°F)
Maximum altitude above sea level without derating
1000 m (3281 ft)
Maximum altitude above sea level with derating
3000 m (9843 ft)
Safety standards
EN/IEC 61800-5-1
EMC standards, Emission
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-3-12, EN 61000-6-1/2, EN 61000-4-2, EN
61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
AQ367426199594en-000101 / 130R0988 | 51Danfoss A/S © 2021.06
Specifications
VLT® HVAC Drive FC 131
Operating Guide

Table of Contents

Related product manuals