[0] No operation
[45] Bus ctrl.
[48] Bus ctrl., timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque relative to limit
[105] Torque relative to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[113] Ext. Closed-loop
[114] Ext. Closed-loop
[115] Ext. Closed-loop
5-60 Terminal 27 Pulse Output Variable
Option: Function:
[0] * No operation Same options and functions as par. 5-6*.
Select the operation variable assigned for terminal 27 readouts.
This parameter cannot be adjusted while the motor is running.
[45] Bus ctrl.
[48] Bus ctrl., timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[113] Ext. Closed-loop 1
[114] Ext. Closed-loop 2
[115] Ext. Closed-loop 3
5-62 Pulse Output Max Freq #27
Range: Function:
5000 Hz* [0 - 32000 Hz] Set the maximum frequency for terminal 27, corresponding to the output variable selected in par.
5-60
Terminal 27 Pulse Output Variable
.
This parameter cannot be adjusted while the motor is running.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-77
3