[1675] Analog In X30/11
[1676] Analog In X30/12
[1677] Analog Out X30/8 [mA]
[1684] Comm. Option Status
[1685] FC Port CTW 1
[1690] Alarm Word
[1691] Alarm word 2
[1692] Warning Word
[1693] Warning word 2
[1694] Ext. Status Word
[1695] Ext. Status Word 2
[1696] Maintenance Word
[1830] Analog Input X42/1
[1831] Analog Input X42/3
[1832] Analog Input X42/5
[1833] Analog Out X42/7 [V]
[1834] Analog Out X42/9 [V]
[1835] Analog Out X42/11 [V]
10-13 Warning Parameter
Range: Function:
0 N/A* [0 - 65535 N/A] View a DeviceNet-specific warning word. One bit is assigned to every warning. Refer to the Devi-
ceNet Instruction Manual (MG.33.DX.YY) for further information.
Bit:
Meaning:
0 Bus not active
1 Explicit connection timeout
2 I/O connection
3 Retry limit reached
4 Actual is not updated
5CAN bus off
6 I/O send error
7 Initialization error
8 No bus supply
9Bus off
10 Error passive
11 Error warning
12 Duplicate MAC ID Error
13 RX queue overrun
14 TX queue overrun
15 CAN overrun
10-14 Net Reference
Read only from LCP
Option: Function:
Select the reference source in instance 21/71 and 20/70.
[0] * Off Enables reference via analog/digital inputs.
[1] On Enables reference via the serial communication bus.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-114
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals