10-13 Warning Parameter
Range: Function:
0 N/A* [0 - 65535 N/A] View a DeviceNet-specific warning word. One bit is assigned to every warning. Refer to the Devi-
ceNet Instruction Manual (MG.33.DX.YY) for further information.
Bit:
Meaning:
0 Bus not active
1 Explicit connection timeout
2 I/O connection
3 Retry limit reached
4 Actual is not updated
5CAN bus off
6 I/O send error
7 Initialization error
8 No bus supply
9Bus off
10 Error passive
11 Error warning
12 Duplicate MAC ID Error
13 RX queue overrun
14 TX queue overrun
15 CAN overrun
10-14 Net Reference
Read only from LCP
Option: Function:
Select the reference source in instance 21/71 and 20/70.
[0] * Off Enables reference via analog/digital inputs.
[1] On Enables reference via the serial communication bus.