[41] Reset Trip This event is TRUE if the adjustable frequency drive is tripped (but not trip-locked) and the reset
button is pressed.
[42] Auto Reset Trip This event is TRUE if the adjustable frequency drive is tripped (but not trip-locked) and an automatic
reset is issued.
[43] OK Key This event is TRUE if the OK key on the LCP is pressed.
[44] Reset Key This event is TRUE if the Reset key on the LCP is pressed.
[45] Left Key This event is TRUE if the Left key on the LCP is pressed.
[46] Right Key This event is TRUE if the Right key on the LCP is pressed.
[47] Up Key This event is TRUE if the Up key on the LCP is pressed.
[48] Down Key This event is TRUE if the Down key on the LCP is pressed.
[50] Comparator 4 Use the result of comparator 4 in the logic rule.
[51] Comparator 5 Use the result of comparator 5 in the logic rule.
[60] Logic rule 4 Use the result of logic rule 4 in the logic rule.
[61] Logic rule 5 Use the result of logic rule 5 in the logic rule.
[70] SL Timeout 3 Use the result of timer 3 in the logic rule.
[71] SL Timeout 4 Use the result of timer 4 in the logic rule.
[72] SL Timeout 5 Use the result of timer 5 in the logic rule.
[73] SL Timeout 6 Use the result of timer 6 in the logic rule.
[74] SL Timeout 7 Use the result of timer 7 in the logic rule.
[80] No Flow
[81] Dry Pump
[82] End of Curve
[83] Broken Belt
13-03 Reset SLC
Option: Function:
[0] * Do not reset SLC Retains programmed settings in all group 13 parameters (13-*).
[1] Reset SLC Resets all group 13 parameters (13-*) to default settings.