[38] Digital input DI33
[39] Start command
[40] Drive stopped
[41] Reset Trip
[42] Auto Reset Trip
[43] OK Key
[44] Reset Key
[45] Left Key
[46] Right Key
[47] Up Key
[48] Down Key
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
[70] SL Timeout 3
[71] SL Timeout 4
[72] SL Timeout 5
[73] SL Timeout 6
[74] SL Timeout 7
[80] No Flow
[81] Dry Pump
[82] End of Curve
[83] Broken Belt
13-43 Logic Rule Operator 2
Array [6]
Option: Function:
Select the second logical operator to be used on the Boolean input calculated in par.13-40
Logic
Rule Boolean 1
, par.13-41
Logic Rule Operator 1
, and par.13-42
Logic Rule Boolean 2
, and the
Boolean input coming from par.13-42
Logic Rule Boolean 2
.
[13-44] signifies the Boolean input of par.13-44
Logic Rule Boolean 3
.
[13-40/13-42] signifies the Boolean input calculated in par.13-40
Logic Rule Boolean 1
, par.
13-41
Logic Rule Operator 1
, and par.13-42
Logic Rule Boolean 2
. DISABLED [0] (factory setting).
select this option to ignore par.13-44
Logic Rule Boolean 3
.
[0] * DISABLED
[1] AND
[2] OR
[3] AND NOT
[4] OR NOT
[5] NOT AND
[6] NOT OR
[7] NOT AND NOT
[8] NOT OR NOT