[28] Freeze output Freezes the output frequency of the adjustable frequency drive.
[29] Start timer 0 Starts timer 0, see par.13-20
SL Controller Timer
for further description.
[30] Start timer 1 Starts timer 1, see par.13-20
SL Controller Timer
for further description.
[31] Start timer 2 Starts timer 2, see par.13-20
SL Controller Timer
for further description.
[32] Set digital out A low Any output with ‘digital output 1’ selected is low (off).
[33] Set digital out B low Any output with ‘digital output 2’ selected is low (off).
[34] Set digital out C low Any output with ‘digital output 3’ selected is low (off).
[35] Set digital out D low Any output with ‘digital output 4’ selected is low (off).
[36] Set digital out E low Any output with ‘digital output 5’ selected is low (off).
[37] Set digital out F low Any output with ‘digital output 6’ selected is low (off).
[38] Set digital out A high Any output with ‘digital output 1’ selected is high (closed).
[39] Set digital out B high Any output with ‘digital output 2’ selected is high (closed).
[40] Set digital out C high Any output with ‘digital output 3’ selected is high (closed).
[41] Set digital out D high Any output with ‘digital output 4’ selected is high (closed).
[42] Set digital out E high Any output with ‘digital output 5’ selected is high (closed).
[43] Set digital out F high Any output with ‘digital output 6’ selected is high (closed).
[60] Reset Counter A Resets Counter A to zero.
[61] Reset Counter B Resets Counter A to zero.
[70] Start Timer 3 Starts timer 3, see par.13-20
SL Controller Timer
for further description.
[71] Start Timer 4 Starts timer 4, see par.13-20
SL Controller Timer
for further description.
[72] Start Timer 5 Starts timer 5, see par.13-20
SL Controller Timer
for further description.
[73] Start Timer 6 Starts timer 6, see par.13-20
SL Controller Timer
for further description.
[74] Start Timer 7 Starts timer 7, see par.13-20
SL Controller Timer
for further description.
[80] Sleep Mode
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-133
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals