[2] Initialization Select
Initialization
[2] to reset all parameter values to default settings, except for par.15-03
Power-
ups
, par.15-04
Over Temps
and par.15-05
Over Volts
. The adjustable frequency drive will reset
during the next power-up.
par.14-22
Operation Mode
will also revert to the default setting
Normal operation
[0].
[3] Boot mode
14-25 Trip Delay at Torque Limit
Range: Function:
60 s* [0 - 60 s] Enter the torque limit trip delay in seconds. When the output torque reaches the torque limits (par.
4-16
Torque Limit Motor Mode
and par.4-17
Torque Limit Generator Mode
), a warning is triggered.
When the torque limit warning has been continuously present for the period specified in this pa-
rameter, the adjustable frequency drive trips. Disable the trip delay by setting the parameter to 60
s = OFF. Thermal adjustable frequency drive monitoring will still remain active.
14-26 Trip Delay at Inverter Fault
Range: Function:
0. s* [0 - 35 s] When the adjustable frequency drive detects an overvoltage in the set time, tripping will be affected
after the set time.
14-29 Service Code
Range: Function:
0 N/A* [-2147483647 - 2147483647 N/A] Service use only.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-139
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage