[2] Initialization Select
Initialization
[2] to reset all parameter values to default settings, except for par.15-03
Power-
ups
, par.15-04
Over Temps
and par.15-05
Over Volts
. The adjustable frequency drive will reset
during the next power-up.
par.14-22
Operation Mode
will also revert to the default setting
Normal operation
[0].
[3] Boot mode
14-25 Trip Delay at Torque Limit
Range: Function:
60 s* [0 - 60 s] Enter the torque limit trip delay in seconds. When the output torque reaches the torque limits (par.
4-16
Torque Limit Motor Mode
and par.4-17
Torque Limit Generator Mode
), a warning is triggered.
When the torque limit warning has been continuously present for the period specified in this pa-
rameter, the adjustable frequency drive trips. Disable the trip delay by setting the parameter to 60
s = OFF. Thermal adjustable frequency drive monitoring will still remain active.
14-26 Trip Delay at Inverter Fault
Range: Function:
0. s* [0 - 35 s] When the adjustable frequency drive detects an overvoltage in the set time, tripping will be affected
after the set time.
14-29 Service Code
Range: Function:
0 N/A* [-2147483647 - 2147483647 N/A] Service use only.