EasyManua.ls Logo

Danfoss VLT HVAC Series

Danfoss VLT HVAC Series
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16-71 Relay Output [bin]
Range: Function:
0 N/A* [0 - 31 N/A] View the settings of all relays.
16-72 Counter A
Range: Function:
0 N/A* [-2147483648 - 2147483647 N/A] View the present value of Counter A. Counters are useful as comparator operands, see par.
13-10
Comparator Operand
.
The value can be reset or changed either via digital inputs (parameter group 5-1*) or by using an
SLC action (par.13-52
SL Controller Action
).
16-73 Counter B
Range: Function:
0 N/A* [-2147483648 - 2147483647 N/A] View the present value of Counter B. Counters are useful as comparator operands (par.13-10
Com-
parator Operand
).
The value can be reset or changed either via digital inputs (parameter group 5-1*) or by using an
SLC action (par.13-52
SL Controller Action
).
16-75 Analog In X30/11
Range: Function:
0.000 N/A* [-20.000 - 20.000 N/A] View the actual value at input X30/11 of MCB 101.
16-76 Analog In X30/12
Range: Function:
0.000 N/A* [-20.000 - 20.000 N/A] View the actual value at input X30/12 of MCB 101.
16-77 Analog Out X30/8 [mA]
Range: Function:
0.000 N/A* [0.000 - 30.000 N/A] View the actual value at input X30/8 in mA.
3.16.7 16-8* Ser. Com. Bus & Adjustable Frequency Drive Port
Parameters for reporting the BUS references and control words.
16-80 Fieldbus CTW 1
Range: Function:
0 N/A* [0 - 65535 N/A] View the two-byte control word (CTW) received from the bus master. Interpretation of the control
word depends on the serial communication bus option installed and the control word profile selected
in par.8-10
Control Profile
.
For more information, refer to the relevant serial communication bus manual.
3 Parameter Description VLT
®
HVAC Drive Programming Guide
3-158
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3

Related product manuals