NOTE!
When mounting an Analog I/O MCB109 option card, a battery back-up of the date and time is included.
23-64 Timed Period Stop
Range: Function:
0 N/A* [0 - 0 N/A] Set the date and time at which the trend analyses must stop update of the timed bin counters.
Date format will depend on setting in par.0-71
Date Format
, and time format on setting in par.
0-72
Time Format
.
NOTE!
When mounting an Analog I/O MCB109 option card, a battery back-up of the date and time is included.
23-65 Minimum Bin Value
Range: Function:
0 %* [0 - 100. %] Array with 10 elements ([0]–[9] below parameter number in display). Press OK and step between
elements by means of
▲
and
▼
buttons on the LCP.
Set the minimum limit for each interval in par.23-61
Continuous Bin Data
and par.23-62
Timed Bin
Data
. Example: if selecting
counter
[1] and changing setting from 10% to 12%,
counter
[0] will be
based on the interval 0%–<12% and
counter
[1] on interval 12%–<20%.
23-66 Reset Continuous Bin Data
Option: Function:
Select
Do reset
[1] to reset all values in par.23-61
Continuous Bin Data
.
After pressing OK, the setting of the parameter value will automatically change to
Do not reset
[0].
[0] * Do not reset
[1] Do reset
23-67 Reset Timed Bin Data
Option: Function:
Select
Do reset
[1] to reset all counters in par.23-62
Timed Bin Data
.
After pressing OK, the setting of the parameter value will automatically change to
Do not reset
[0].
[0] * Do not reset
[1] Do reset
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-225
3