EasyManuals Logo

Danfoss VLT HVAC Series User Manual

Danfoss VLT HVAC Series
338 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #87 background imageLoading...
Page #87 background image
[85] SL Digital Output F See par.13-52
SL Controller Action
. The input will go high whenever the Smart Logic Action [43]
Set dig. out. F high
is executed. The input will go low whenever the Smart Logic Action [37]
Set dig.
out. F low
is executed.
[160] No alarm The output is high when no alarm is present.
[161] Running reverse The output is high when the adjustable frequency drive is running counter-clockwise (the logical
product of the status bits ‘running’ AND ‘reverse’).
[165] Local reference active The output is high when par.3-13
Reference Site
= [2] Local or when par.3-13
Reference Site
= [0]
Linked to hand auto
at the same time as the LCP is in [Hand on] mode.
[166] Remote reference active The output is high when par.3-13
Reference Site
[1] or
Linked to hand/auto
[0] while the LCP is in
[Auto on] mode.
[167] Start command active The output is high when there is an active Start command (i.e., via digital input bus connection or
[Hand on] or [Auto on], and no Stop or Start command is active.
[168] Drive in hand mode The output is high when the adjustable frequency drive is in Hand on mode (as indicated by the
LED light above [Hand on].
[169] Drive in auto mode The output is high when the adjustable frequency drive is in Hand on mode (as indicated by the
LED light above [Auto on].
[180] Clock Fault The clock function has been reset to default (2000-01-01) because of a power failure.
[181] Preventive Maintenance One or more of the preventive maintenance events programmed in par.23-10
Maintenance Item
has passed the time for the specified action in par.23-11
Maintenance Action
.
[190] No-Flow A no-flow situation or minimum speed situation has been detected if enabled in par.22-21
Low Power
Detection
and/or par.22-22
Low Speed Detection
.
[191] Dry Pump A dry pump condition has been detected. This function must be enabled in par.22-26
Dry Pump
Function
.
[192] End of Curve A pump running with max. speed for a period of time without reaching the set pressure has been
detected. To enable this function, see par.22-50
End of Curve Function
.
[193] Sleep Mode The adjustable frequency drive/system has set to sleep mode. See par. 22-4*.
[194] Broken Belt A broken belt condition has been detected. This function must be enabled in par.22-60
Broken Belt
Function
.
[195] Bypass Valve Control The bypass valve control (Digital/Relay output in the adjustable frequency drive) is used for com-
pressor systems to unload the compressor during start-up by using a bypass valve. After the Start
command is given, the bypass valve will be open until the adjustable frequency drive reaches par.
4-11
Motor Speed Low Limit [RPM]
) . After the limit has been reached the bypass valve will be
closed, allowing the compressor to operate normally. This procedure will not be activated again
before a new start is initiated and the adjustable frequency drive speed is zero during the receiving
of start signal. par.1-71
Start Delay
can be used in order to delay the motor start. The bypass valve
control principle:
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-63
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage

Related product manuals