EasyManua.ls Logo

Danfoss VLT Midi Drive FC 280

Danfoss VLT Midi Drive FC 280
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Frequency converter
typical shaft output [kW (hp)]
P4K0
4
(5.5)
P5K5
5.5
(7.5)
P7K5
7.5
(10)
P11K
11
(15)
P15K
15
(20)
P18K
18.5
(25)
P22K
22
(30)
Enclosure protection rating IP20 (IP21/Type 1 as
option)
K2 K2 K3 K4 K4 K5 K5
Output current
Shaft output 4 5.5 7.5 11 15 18.5 22
Continuous (3x380–440 V) [A] 9 12 15.5 23 31 37 42.5
Continuous (3x441–480 V) [A] 8.2 11 14 21 27 34 40
Intermittent (60 s overload) [A] 14.4 19.2 24.8 34.5 46.5 55.5 63.8
Continuous kVA (400 V AC) [kVA] 6.2 8.3 10.7 15.9 21.5 25.6 29.5
Continuous kVA (480 V AC) [kVA] 6.8 9.1 11.6 17.5 22.4 28.3 33.3
Maximum input current
Continuous (3x380–440 V) [A] 8.3 11.2 15.1 22.1 29.9 35.2 41.5
Continuous (3x441–480 V) [A] 6.8 9.4 12.6 18.4 24.7 29.3 34.6
Intermittent (60 s overload) [A] 13.3 17.9 24.2 33.2 44.9 52.8 62.3
More specications
Maximum cable cross-section (mains, motor,
brake, and load sharing) [mm
2
(AWG)]
4 (12) 16 (6)
Estimated power loss at rated maximum load
[W]
1)
115.5 157.5 192.8 289.5 393.4 402.8 467.5
Weight enclosure protection rating IP20 [kg (lb)] 3.6 (7.9) 3.6 (7.9) 4.1 (9.0) 9.4 (20.7) 9.5 (20.9) 12.3 (27.1) 12.5 (27.6)
Weight enclosure protection rating IP21 [kg (lb)] 5.5 (12.1) 5.5 (12.1) 6.5 (14.3) 10.5 (23.1) 10.5 (23.1) 14.0 (30.9) 14.0 (30.9)
Eciency [%]
2)
98.0 97.8 97.7 98.0 98.1 98.0 98.0
Table 9.2 Mains Supply 3x380–480 V AC
Frequency converter
typical shaft output [kW (hp)]
PK37
0.37
(0.5)
PK55
0.55
(0.75)
PK75
0.75
(1.0)
P1K1
1.1
(1.5)
P1K5
1.5
(2.0)
P2K2
2.2
(3.0)
P3K7
3.7
(5.0)
Enclosure protection rating IP20 (IP21/Type 1 as
option)
K1 K1 K1 K1 K1 K2 K3
Output current
Continuous (3x200–240 V) [A] 2.2 3.2 4.2 6 6.8 9.6 15.2
Intermittent (60 s overload) [A] 3.5 5.1 6.7 9.6 10.9 15.4 24.3
Continuous kVA (230 V AC) [kVA] 0.9 1.3 1.7 2.4 2.7 3.8 6.1
Maximum input current
Continuous (3x200–240 V) [A] 1.8 2.7 3.4 4.7 6.3 8.8 14.3
Intermittent (60 s overload) [A] 2.9 4.3 5.4 7.5 10.1 14.1 22.9
More specications
Maximum cable cross-section (mains, motor,
brake, and load sharing) [mm
2
(AWG)]
4 (12)
Estimated power loss at rated maximum load
[W]
1)
29.4 38.5 51.1 60.7 76.1 96.1 147.5
Weight enclosure protection rating IP20 [kg
(lb)]
2.3 (5.1) 2.3 (5.1) 2.3 (5.1) 2.3 (5.1) 2.3 (5.1) 2.5 (5.5) 3.6 (7.9)
Weight enclosure protection rating IP21 [kg
(lb)]
4.0 (8.8) 4.0 (8.8) 4.0 (8.8) 4.0 (8.8) 4.0 (8.8) 5.5 (12.1) 6.5 (14.3)
Eciency [%]
2)
96.4 96.6 96.3 96.6 96.5 96.7 96.7
Table 9.3 Mains Supply 3x200–240 V AC
Specications
VLT
®
Midi Drive FC 280
54 Danfoss A/S © 10/2017 All rights reserved. MG07A402
99

Table of Contents

Other manuals for Danfoss VLT Midi Drive FC 280

Related product manuals