Enclosure size Power [kW (hp)] Non-UL fuse
Non-UL circuit breaker
(Eaton)
3-phase 380–480 V
K1
0.37 (0.5)
gG-10
PKZM0-16
0.55–0.75
(0.75–1.0)
1.1–1.5
(1.5–2.0)
gG-20
2.2 (3.0)
K2
3.0–5.5
(4.0–7.5)
gG-25
PKZM0-20
K3 7.5 (10) PKZM0-25
K4
11–15
(15–20)
gG-50
K5
18.5–22
(25–30)
gG-80
3-phase 200–240 V
K1
0.37 (0.5) gG-10
PKZM0-16
0.55 (0.75)
gG-20
0.75 (1.0)
1.1 (1.5)
1.5 (2.0)
K2 2.2 (3.0)
gG-25
PKZM0-20
K3 3.7 (5.0) PKZM0-25
Single-phase 200–240 V
K1
0.37 (0.5) gG-10
PKZM0-16
0.55 (0.75)
gG-20
0.75 (1.0)
1.1 (1.5)
1.5 (2.0)
K2 2.2 (3.0) gG-25 PKZM0-20
Table 9.6 Non-UL Fuse and Circuit Breaker