Setting the PROFIBUS address with set station address
command
1. Switch o the supply.
2. Set the DIP switch to 126 or 127 (factory switch
setting).
3. Set the address via the set station address
command. Use the set station address command
to lock the programmed address and to change
the address. To unlock the address setting,
change parameter 9-18 Node Address or the
address switch, followed by a power cycle. A new
address is eective immediately after applying
the set station address command.
3.2 Congure the Master
3.2.1 GSD File
To congure a PROFIBUS master, the conguration tool
needs a GSD le for each type of slave on the network.
The GSD le is a PROFIBUS DP standard text le containing
the necessary communications set-up data for a slave.
Download the GSD
le for the relevant frequency
converter series vlt-drives.danfoss.com/products/engineering-
software/software-download/eldbus/.
PROFIBUS SW version
(parameter 15-61 Option SW
Version)
GSD le
1.x da01040A.GSD
2.x da02040A.GSD
FCD 302 da01040B.GSD
Table 3.2 GSD File
The following example shows the procedure of
conguring
a PROFIBUS master for FC 301/FC 302, but the procedure is
also valid for other frequency converter series.
1. Import the GSD
le in the conguration tool.
2. Import the GSD le to the Simatic Manager
software tool. Import a GSD le once only for
each frequency converter series, following the
initial installation of the software tool. See
Illustration 3.3.
3. Use the browser for the GSD le, install all les,
and import both a GSD le and a bitmap for the
device into the hardware catalog. See
Illustration 3.4 and Illustration 3.5.
Illustration 3.3 Install GSD File
Illustration 3.4 Import a GSD File and a Bitmap
Illustration 3.5 Add a GSD File
Conguration Programming Guide
MG37G202 Danfoss A/S © 01/2016 All rights reserved. 9
3 3