EasyManua.ls Logo

Danfoss VLT PROFIBUS DP MCA 101 - Example 4: PLC Programming

Danfoss VLT PROFIBUS DP MCA 101
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 7.6 indicates the bit functions and the corresponding bit values which are active for this example.
Bit Bit value=0 Bit value=1 Bit value
00 Control not ready Control ready 1
7
01 Drive not ready Drive ready 1
02 Coasting Enable 1
03 No error Trip 0
04 No error Error (no trip) 0
0
05 Reserved 0
06 No error Trip lock 0
07 No warning Warning 0
08 Speed reference Speed = reference 1
F
09 Local operation Bus control 1
10 Outside frequency range Within frequency range 1
11 No operation In operation 1
12 Drive OK Stopped, auto start 0
0
13 Voltage OK Voltage exceeded 0
14 Torque OK Torque exceeded 0
15 Timers OK Timers exceeded 0
Function active
Function inactive
Table 7.6 Active Bit Functions for Status Word Telegram using PPO Type
7.4
Example 4: PLC Programming
In this example, PPO type 6 is placed in the input/output address, see Illustration 7.2 and Table 7.7.
Illustration 7.2 FC 302 and PPO Type 6 PCD
Input
address
256–257 258–259 260–261 262–263 Output
address
256–257 258–259 260–261 262–263
Set-up Status word MAV Motor
torque
Digital
input
Set-up Control
word
Reference Not used Not used
Table 7.7 Input/Output Address Set-up
Application Examples Programming Guide
MG37G202 Danfoss A/S © 01/2016 All rights reserved. 51
7 7

Table of Contents

Other manuals for Danfoss VLT PROFIBUS DP MCA 101

Related product manuals